Single channel humidity controller URM72
 
SINGLE CHANNEL Regulator - URM72 is a universal controller that allows control of a given process. Allows you to adjust both the hysteresis and using advanced PID with auto tuning function. Extensive measurement input enables you to collaborate with a wide range of sensors such as sensors, resistive (eg Pt100), thermocouple, sensors with current output 0-20mA or 4-20mA, or a voltage output 0-1V.
Two, large, four - tail displays (red, blue, or green) represent the current measured value, and setting which makes handling very easy and much easier to work.
Versatility solution, and a wide range of attachable sensors allows you to use this device to control various processes such as heating, cooling, cooking, drying, pressure control, level, etc.
Controller with connected humidity sensor acts as a humidity regulator
- implemented functions:
- maintain the set value (eg temperature, humidity)
- process Control - Number of measuring inputs: 1
- wide range of sensors connectable
- Control Option: contactors, triacs, thyristors
- type of control: PID or hysteresis
- PID parameters can be programmed by the user
- Sound and light alarm signals:
- exceeding the limit value (eg temperature)
- sensor failure - non-volatile memory to memorize the set of parameters
- continuation of the process after a power interruption.
| inputs | One universal measurement input | It works with sensors: resistance sensors Pt100, Pt1000,Pt500, Ni100. Thermocouples J, K, N, S, R, B. Sensors for linear output 0-1V, 4-20mA, or 0-20mA Digital humidity measurement system UPW's TELDREAM |
| resolution of measurement | 0,1% range - 10 bit ADC 0,025% range - 12-bit converter (optional) |
|
| output | One contact output (optional input) | 5A/250VAC, resistive load (5VDC, 9VDC optional) |
| One voltage output | Typically, you can connect an external buzzer or light | |
| programming | The programming | With the keyboard, two modes of operation: programming, normal operation |
| The security parameters of the programming | Automatic locking when working | |
| control | control Method | Hysteresis - programmable hysteresis PID – programmable control parameters Others on request (eg three-way valve control) |
| Power Supply | voltage | 230 VAC, 24VAC, 12VAC, 8-32VDC |
| Power consumption | 1,5VA | |
| alarms | Exceeding the scope of | The signal light and sound - pulsing |
| sensor failure | Light and sound signal - a continuous | |
| other | memory | Protection against power outages, Enduring memory parameter setting value |
| digital display | 4 + 4 digits (red, green, or blue - 14mm) | |
| degree of protection | From the front IP65 (with seal), total IP20 | |
| operating temperature | 0 - 60 °C | |
| humidity | 80% without condensation | |
| weight | 300g | |
| Sizes | WxSxG (72x72x80mm) | |
| Mounting Hole Dimension | WxS (69x69mm) | |
| Mounting plate thickness | to 6mm | |
| Faceplate Color | gray (other by arrangement) |
Description of terminals

Types of measuring inputs
| code | sensor | range |
| 1 | Thermocouple J | 0 - 800°C |
| 2 | Thermocouple K | 0 - 1200°C |
| 3 | Thermocouple N | 0 - 1300°C |
| 4 | Thermocouple S | 0 - 1500°C |
| 5 | Thermocouple R | 0 - 1500°C |
| 6 | Thermocouple B | 0 - 1700°C |
| 7 | Pt100 | -200 - 750°C |
| 8 | Pt500 | -200 - 750°C |
| 9 | Pt1000 | -200 - 750°C |
| 10 | Ni100 | -60 - 180°C |
| 11 | 0 - 1 V | ------- |
| 12 | 0 - 20 mA | ------- |
| 13 |
4 - 20 mA UPW |
------- 0 - 100% |